600 Volts. Copper Conductor. PVC Insulation/Nylon Sheath THHN/THWN. Heat, Moisture, Gasoline and Oil Resistant II.Silicone-Free.
1. Conductor: Solid sizes 14 - 10 AWG use soft drawn annealed bare copper per ASTM B3. Stranded sizes 14 - 10 AWG use combination-unilay soft drawn annealed bare copper per ASTM B3 and B787.
2. Insulation: Heat and moisture resistant Polyvinyl Chloride (PVC)
3. Sheath: Nylon
APPLICATION
Southwire THHN copper conductors are primarily used in conduit for branch circuits in commercial or industrial applications as specified in the National Electrical Code® and other applicable codes and standards. Voltage for all applications is 600 volts. These conductors have multiple ratings depending upon the product application. Allowable temperatures are as follows:
• THHN or T90 Nylon: Dry locations not to exceed 90°C
• THWN: Wet locations not to exceed 75°C or dry locations not to exceed 90°C or locations not to exceed 75°C when exposed to oil
• TWN75: Wet locations not to exceed 75°C
• MTW: Wet locations or when exposed to oil at temperatures not to exceed 60°C or dry locations not to exceed 90°C (with ampacity limited to that for 75°C conductor temperature per NFPA 79)
• AWM: Dry locations not to exceed 105°C only when rated and used as appliance wiring material
FEATURES
• Gasoline and Oil Resistant II
• VW-1: Sizes 14 through 10 AWG
• FT1: All Sizes
• AWM: Sizes 14 through 10 AWG
• MTW: Stranded Constructions Only
• RoHS Compliant
• ASTM B3 Soft or Annealed Copper Wire
• ASTM B787 19 Wire Combination Unilay-Stranded Copper Conductors
• UL 83 Thermoplastic Insulated Wires and Cables
• UL 758 Standard for Appliance Wiring Material
• UL 1063 Machine Tool Wiring (MTW)
• CSA C22.2 No. 75 Thermoplastic Insulated Wires and Cables
• ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
• Federal Specification A-A-59544
• NMX-J-010-ANCE Thermoplastic insulated wires and cables
• NOM-063-SCFI Electrical Products – Conductors – Safety Requirements
• NEMA 70901-2-2024 Make It American Compliance with Domestic Preference Requirements Pt. 2 Wire & Cable
| Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @75°C | Inductive Reactance @ 60Hz | Allowable Ampacity At 75°C | Allowable Ampacity At 90°C | |
| AWG/ | inch | lb | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | |
| Kcmil | ||||||||
| 14 | 0.4 | 32 | 2.631 | 3.17 | 0.058 | 20 | 25 | |
| 12 | 0.5 | 52 | 1.662 | 2.002 | 0.054 | 25 | 30 | |
| 10 | 0.6 | 83 | 1.04 | 1.253 | 0.05 | 35 | 40 | |
| 14 | 0.5 | 32 | 2.631 | 3.17 | 0.058 | 20 | 25 | |