Power Cable 600 or 1000 Volt Single Conductor Copper, Cross Linked Polyethylene (XLPE). Silicone Free
1. Conductor: Solid or Class B compressed stranded bare copper per ASTM B3 and ASTM B8
2. Insulation: Cross Linked Polyethylene (XLPE)
APPLICATION
Southwire XHHW-2 copper conductors circuit sizes are primarily used in conduit, or other recognized raceways, and branch circuit wiring, as specified in the National Electrical Code. XHHW-2 copper conductors may be used in wet or dry locations at temperatures not to exceed 90°C. Voltage rating for XHHW-2 conductors is 600 volts or 1000 volts. Suitable for use in Health Care Facilities per Section 517.160 of the National Electrical Code where a dielectric constant of less than 3.5 maybe specified.
FEATURES
- SIS - Sizes 14 AWG through 10 AWG
- RoHS Compliant
• ASTM B3 Soft or Annealed Copper Wire
• ASTM B8 Concentric-Lay-Stranded Copper Conductors
• UL 44 Thermoset-Insulated Wires and Cables
• ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
• Made in America: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661
• Federal Specification A-A-59544
• NMX-J-451-ANCE Thermoset insulated wires and cables
• NOM-063-SCFI Electrical Products – Conductors – Safety Requirements
NEMA 70901-2-2024 Make It American Compliance with Domestic Preference Requirements Pt. 2 Wire & Cable
| Cond. Size | Strand Count | Diameter Over Conductor | Insul. Thickness | Insulation Color | Approx. OD | Copper Weight | Approx. Weight |
| AWG/Kcmil | No. of Strands | inch | mil | inch | lb/1000ft | lb/1000ft | |
| 14 | Solid | 0.064 | 30 | PK | 0.131 | 12 | 17 |
| 14 | 7 | 0.07 | 30 | PE | 0.131 | 12 | 17 |
| 12 | 7 | 0.088 | 30 | PE | 0.147 | 20 | 24 |
| 10 | 7 | 0.113 | 30 | BK | 0.173 | 32 | 36 |